|
CONCRETE
PAD :
The dimensions of the concrete pad will vary depending
on the layout of the equipment chosen. It is recommended
to have a minimum of 5 ft. clearance in front of the
sterilizers for loading and a minimum of 3 ft. behind
the chambers for access. The length should be 5 ft.
greater than the combined length of the San-I-Pak
Sterilizers. "The concrete pad must be level,
with no more than 1/2" slope side to side, or
end to end." If the San-I-Pak will be mounted
on a dock, the dock must also be level. If there will
be variations, call the factory for assistance in
determining suitability. If a pad is already present
at the proposed installation site, insure it conforms
with the standards above. The 2P Sterilizer is designed
for indoor or outdoor installation. A level surface
able to support 1,640 to 1,715 pounds is required.
ANCHORING:
If it is required that the San-I-Pak be anchored to
the floor, (check local regulations) use four (4)
3/8" x 3" long multi-set anchor bolts. To
allow for construction variations, it is best if the
holes are drilled in the floor after the San-I-Pak
is placed in position. The holes in the base plates
are oversized to permit the use of a 3/8" concrete
drill. Shim to compensate for any floor unevenness
and then tighten all bolts securely.
DRAIN:
The San-I-Pak requires a drain for the condensate
discharge and steam generator blow down, if so equipped.
The drain should be a floor type. The discharge end
of the condensate tank should be plumbed with a minimum
1" copper or black pipe and air gapped above
the floor drain.
ELECTRICAL:
The San-I-Pak unit requires a 120 VAC control circuit.
The control voltage circuit should be a minimum of
15 amps and be dedicated just to the unit.
If
the unit is equipped with the optional steam generator,
a single phase 240 VAC, or 3 phase power source will
also be required. Also the control voltage circuit
should be increased to 20 amps, because a branch will
be used for the generator. The required fused disconnects
for use in conjunction with the steam generator are
as follows: (If not enough power is available, the
unit can be operated utilizing a smaller steam generator.
Please call the factory for assistance.)
Actual
Amperage Draw
|
Electric
Steam Generator:
- 240
Volts, 1 Phase = 84 Amps
- 208
Volts, 3 phase = 56 Amps
- 240
Volts, 3 phase = 49 Amps
- 480
Volts, 3 phase = 24 Amps
|
Steam
Generator, Service Requirements:
-
240 Volts, 1 Phase = 125 Amps
-
208 Volts, 3 phase = 100 Amps
- 240
Volts, 3 phase = 75 Amps
-
480 Volts, 3 phase = 50 Amps
|
Run
power lines between fused disconnect switch (customer
furnished) and the steam generator electrical panel
box, in accordance with local codes.
STEAM
SUPPLY:
If
your unit is not equipped with the optional steam
generator, a connection to your steam line will be
required. A minimum 3/4" insulated line supplying
97% to 100% saturated steam vapor at a maximum flow
rate of 60 lbs./hr. is required. For standard installations,
a minimum steam pressure of 40 psig, maximum of 100
psig is necessary. If the steam pressure is below
100 psig, do not install a PRV in the line. In cases
where only low pressure steam is available, a minimum
of 15 psig can be used. The San-I-Pak will be programmed
to attain a temperature of 250o F., and hold for a
longer period of time. It is recommended that a shut
off valve be installed at the point of connection.
The San-I-Pak unit comes equipped with an inlet strainer
and separate water trap to insure a minimum of water
in the supply line.
WATER
SUPPLY:
A
3/8" diameter line (or larger) at normal city
pressure providing a minimum of 2 gpm is required.
It is recommended that a shutoff valve be installed
at the point of connection. If the unit is to be installed
with the optional steam generator, then a 1/2"
diameter line at normal city pressure providing a
minimum of 8 gpm is required.
DRAIN
LINE:
A
minimum 1-1/2" copper pipe or black pipe is to
be connected to the condensate tank, and plumbed so
as not to create any back pressure. The tank is accessible
by removing the lower rear access panel. It is recommended
that this line be plumbed to a sanitary drain, but
in some cases may be connected to a storm drain depending
on local regulations. All condensate exits from this
line.
|