|
CONCRETE
PAD :
The dimensions of the concrete pad will vary depending
on the layout of the equipment chosen. It is recommended
to have a minimum of 5 ft. clearance in front of the
sterilizers for loading. The length should be 5 ft.
greater than the combined length of the San-I-Pak
200/300 Sterilizers, compactor and roll-off container.
The pad under the compactor and roll-off container
should be a minimum 3,000 psi concrete, steel reinforced,
6" thick. "The concrete pad must be level,
with no more than 1/2" slope side to side, or
end to end." If the San-I-Pak will be mounted
on a dock, the dock must also be level. If there will
be variations, alert the factory for assistance in
determining suitability.
If
a pad is already present at the proposed installation
site, insure it conforms with the standards above.
For good housekeeping practices, we recommend the
installation of a trench drain beneath the area where
the compactor and roll-off container connect. The
pad should be positioned to allow adequate maneuvering
room for the container handling vehicle. Allow a minimum
of 45 ft. of clearance space from container "hook-up"
end for such equipment.
ANCHORING:
The San-I-Pak equipment will be anchored to the concrete
pad using either 5/8" x 4-1/2" or 3/4"
x 6" long anchor bolts. Ramset Trubolt anchors
or equal will be used. The holes will be drilled in
the concrete after the San-I-Pak equipment is placed
in position. The holes in the base plates are oversized
to permit the use of a concrete drill. The installation
personnel will shim to compensate for any pad unevenness
and then tighten all nuts securely. The roll-off container
guide channels will be anchored utilizing 5/8"
x 4-1/2" Ramset Trubolt anchors or equal.
ELECTRICAL:
The San-I-Pak unit requires a 120V control circuit
as well as a 3 phase power source.
1
CHAMBER:
The control voltage circuit should be a minimum of
15 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 30 amps.
2
CHAMBERS:
The control voltage circuit should be a minimum of
20 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 35 amps.
3
CHAMBERS:
The control voltage circuit should be a minimum of
25 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 40 amps.
4
CHAMBERS:
The control voltage circuit should be a minimum of
30 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 45 amps.
5
CHAMBERS:
The control voltage circuit should be a minimum of
35 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 50 amps.
6
CHAMBERS:
The control voltage circuit should be a minimum of
40 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 55 amps.
7
CHAMBERS:
The control voltage circuit should be a minimum of
45 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 60 amps.
8
CHAMBERS:
The control voltage circuit should be a minimum of
50 amps and be dedicated just to the unit. If the
San-I-Pak installed cold weather package is used,
the service must be a minimum of 65 amps.
The
electrical should be stubbed up as shown in the installation
drawing. The electrical can be run from overhead and
attached to the San-I-Pak as long as it doesn't interfere
with the removal of access panels. After the San-I-Pak
has been installed, run the 3 phase power lines between
the fused disconnect switch (customer furnished) and
the San-I-Pak equipment electrical panel box, in accordance
with local codes. This fused disconnect switch should
be sized in accordance with the following specs:
"S"
Compactor
Compactor,
Service Requirements:
208 Volt, 3 Phase = 20 Amp
240 Volt, 3 Phase = 20 Amp
480 Volt, 3 Phase = 15 Amp
"L"
Compactor
Compactor,
Service Requirements:
208 Volt, 3 Phase = 70 Amp
240 Volt, 3 Phase = 60 Amp
480 Volt, 3 Phase = 30 Amp
"SS"
Compactor
Compactor,
Service Requirements:
208 Volt, 3 Phase = 70 Amp
240 Volt, 3 Phase = 60 Amp
480 Volt, 3 Phase = 30 Amp
"MS"
Compactor
Compactor,
Service Requirements:
208 Volt, 3 Phase = 70 Amp
240 Volt, 3 Phase = 60 Amp
480 Volt, 3 Phase = 30 Amp
STEAM
SUPPLY:
The San-I-Pak requires a minimum steam pressure of
65 psig, and is capable of handling a maximum of 125
psig. You are only required to install a pressure
regulating valve (PRV) in the steam line if your pressure
is above 125 psig. If your steam pressure is below
125 psig, do not install a PRV in the line. A return
condensate line is not required. All condensate is
cooled and discharged to the sanitary sewer.
A
1" insulated steam line is required for systems
with 1 to 3 sterilizer chambers & a 1-1/2"
insulated steam line is required for systems with
4 to 8 sterilizer chambers.
The
San-I-Pak requires a minimum of 97% to 100% saturated
steam, poor quality steam is evidenced by excessive
condensate generated during sterilization. It is required
that a shut off valve and a pressure gauge be installed
at the point of connection. The steam line is typically
stubbed up through the concrete pad. If this is not
possible, the steam line may also be run from overhead
and attached to the San-I-Pak so as not to interfere
with the removal of access panels.
The
San-I-Pak unit comes equipped with an inlet strainer
and separate water trap to improve steam quality in
the supply line, but if you have a long run of piping,
it is advisable to install a drip leg with an additional
bucket or thermostatic trap. Insure the steam line
has no low spots that may act as a water trap. The
steam should be generated from treated boiler water
to prevent corrosion and/or buildup in the lines.
WATER
SUPPLY:
Systems
processing 400 lbs/hr. requires 1/2" water line
at a minimum of 30-100 psi.
Systems processing 400-800 lbs/hr. requires 3/4"
water line at a minimum of 30-100 psi.
Systems processing 800-1600 lbs/hr. requires 1"
water line at a minimum of 30-100 psi
Systems processing 1600-3200 lbs/hr. requires 1-1/2"
water line at a minimum of 30-100 psi.
DRAIN:
A floor mount drain should be installed beneath the
San-I-Pak near the connection point of the roll-off
container. Typically this will connect to a sanitary
drain line. For any variances, contact the factory.
A 2" copper or black pipe drain line (1 to 3
chambers) or a 3" copper or black pipe drain
line (4 to 8 chambers) will be connected to the condensate
tank and plumbed so as not to create any back pressure.
All condensate will exit from this line.
PHONE
LINE:
The PLC with remote diagnostic capability is standard
on all sterilizer & compactor systems. A dedicated
phone line, separate from the facility's switchboard,
must be installed into the electrical cabinet. The
phone jack must be a standard A T & T plug in
type (Part Number RJ11C). This is for the modem communication
for troubleshooting assistance and/or the optional
ServNet programming. Note: Warranty not activated
until modem is connected.
|