ONE-STAGE
SHREDDER:
The
3 phase power should be run into a distribution panel
having two separate disconnects. One for the compactor
section and one for the shredder. After the San-I-Pak
has been installed, run power lines between fused
disconnect switches (customer furnished) and San-I-Pak's
electrical panel box, in accordance with local codes.
The fused disconnect switches should be sized in accordance
with the following specs:
15
(One 7.5 HP Motor)
Actual
Amperage Draw:
208
Volt = 24.2 Amp
240
Volt = 22.0 Amp
360
Volt = 12.7 Amp
480
Volt = 11.0 Amp
550
Volt = 09.0 Amp |
Service
Requirements:
208
Volt = 30.0 Amp
240
Volt = 27.5 Amp
360
Volt = 15.8 Amp
480
Volt = 13.7 Amp
550 Volt = 11.3 Amp |
Service
Breaker:
30.0
Amp
30.0
Amp
20.0
Amp
15.0
Amp
15.0
Amp |
From
the Service Requirement Amperages, select the next
highest service from the following available service
breakers 15, 20, 30, 40, 50, 60, 70, 100, 125, 150,
200, 225.
TWO
STAGE SHREDDER:
The
3 phase power should be run into a distribution panel
having two separate disconnects; one for the compactor
section and one for the shredders. After the San-I-Pak
has been installed, run power lines between fused
disconnect switches (customer furnished) and San-I-Pak's
electrical panel box, in accordance with local codes.
The fused disconnect switches should be sized in accordance
with the following specs:
15
(One 7.5 HP Motor)
Actual
Amperage Draw:
208
Volt = 24.2 Amp
240 Volt = 22.0 Amp
360
Volt = 12.7 Amp
480
Volt = 11.0 Amp
550
Volt = 09.0 Amp |
Service
Requirements:
208
Volt = 30.0 Amp
240
Volt = 27.5 Amp
360
Volt = 15.8 Amp
480
Volt = 13.7 Amp
550 Volt = 11.3 Amp |
|
20
(One 15 HP Motor)
Actual
Amperage Draw:
208 Volt = 46.2 Amp
240 Volt = 42.0 Amp
360 Volt = 25.5 Amp
480 Volt = 21.0 Amp
550 Volt = 17.0 Amp |
Service
Requirements:
208 Volt = 57.7 Amp
240 Volt = 52.5 Amp
360 Volt = 31.5 Amp
480
Volt = 26.3 Amp
550 Volt = 21.3 Amp
|
|
25
(One 20 HP Motor)
Actual
Amperage Draw:
208 Volt = 59.4 Amp
240 Volt = 54.0 Amp
360 Volt = 34.0 Amp
480 Volt = 27.0 Amp
550 Volt = 22.0 Amp |
Service
Requirements:
208 Volt = 74.3 Amp
240 Volt = 67.5 Amp
360 Volt = 42.5 Amp
480
Volt = 36.0 Amp
550 Volt = 27.5 Amp
|
|
50
(One 20 HP Motor)
Actual
Amperage Draw:
208 Volt = 59.4 Amp
240 Volt = 54.0 Amp
360 Volt = 34.0 Amp
480 Volt = 27.0 Amp
550 Volt = 22.0 Amp |
Service
Requirements:
208 Volt = 74.3 Amp
240 Volt = 67.5 Amp
360 Volt = 42.5 Amp
480
Volt = 33.8 Amp
550 Volt = 27.5 Amp
|
|
Add
the Service Requirement Amperages, then select the
next highest service from the following available
service breakers 15, 20, 30, 40, 50, 60, 70, 100,
125, 150, 200, 225.
Example:
ST-50 @ 240V = 67.5 Amp
ST-20 @ 240V = 52.5 Amp
120.0 Amp (choose
125 Amp Service Breaker)
ST-20 @ 480V = 26.3 Amp
ST-20 @ 480V = 26.3 Amp
52.6
Amp (choose
60 Amp Service Breaker)
|